Connection diagram for smoke sensor IP 212 45. Purpose and application

Operating principle of the IP 212-45 detector

The fire detector allows you to detect the appearance of smoke on early stage at the place of its installation. When the detector is triggered, its internal resistance decreases and the indicator light becomes constant. The detector is powered and the “Fire” signal is transmitted via a two-wire loop. In standby mode, the indicator blinks at intervals of 1 every 5 seconds.

Scheme for connecting the IP 212-45 detector to a two-wire alarm loop

The fire detector IP 212-45 consists of two main modules - a sensor and a socket. The sensor is an optical-electronic system and radio elements in a plastic case. Convenience of installation, maintenance and time saving is provided by a detachable connection of the sensor to the socket.

The contact base of the IP 212-45 detector is designed on the principle of screwless contacts, which ensures high reliability of electrical contact and saves time during installation.

Short-circuit contacts 3 and 4 allow you to create a “Fault” mode in the PPK alarm loop if the sensor is removed from the socket.

Regular city ​​apartment is quite a fire hazard. The source of ignition can be anything - heated electrical wiring, faulty household appliances or a forgotten iron. The greatest danger in terms of fire is the kitchen. Besides household appliances, which has great power, there is a main danger - open fire. A stove left without constant supervision can cause a lot of trouble. You can find out about a fire in the kitchen without connecting an expensive security and fire system with lots of wires. The autonomous fire detector IP 212 has proven itself well for use at home.

Purpose and application

The IP 212 fire alarm sensor is intended for installation in residential, administrative and utility premises. Its peculiarity is that there is no need for connection to wires, power supplies and information boards.

The sensor is completely autonomous; it receives energy from a battery. The fire detector IP 212 reacts to the appearance of smoke in the room, which gives a light and sound signal.

This device can be installed in the following places:

  1. Residential apartments. The installation location can be a kitchen, a corridor or one of the rooms.
  2. Offices. So as not to spoil new renovation gating walls for wires fire alarm system, you can use the autonomous smoke detector IP 212.
  3. Libraries and archives. As a rule, the rooms in which various archival materials are stored are visited very rarely. These rooms are quite large and are not visible visually.

As a rule, all buildings and structures are built and renovated on a turnkey basis. Laying new communications requires time and money. In essence, this is a repair, with all its consequences. Installation of autonomous sensors is the best option, both for the safety of premises owners and to meet the requirements of regulatory authorities.

For residential apartments the installation of such devices is a unique opportunity to find out about a fire at an early stage, when the fire is small and you can extinguish it yourself.

Device and principle of operation

Firefighter smoke detector IP 212 has a fairly simple device. It is designed for do-it-yourself installation without the involvement of specialists.

The detector consists of the following parts:

  1. Housing made of white durable plastic.
  2. Printed circuit board, which is a monitoring and control element.
  3. Sound membrane.
  4. Optical block.
  5. Indicator light.
  6. Battery compartment.
  7. Battery type "6F22".
  8. Fastening material (screws and plastic dowels).

No high voltage and open contacts do not require special education and complex tools for installation and handling of the device.

On a note: The operating principle of the IP 212 detector is based on a change in the electrical parameters of the photodiode, due to the weakening of the strength of the light pulse due to smoke particles.

The photodiode has greater sensitivity and the device operates at a minimum smoke concentration.

When detecting smoke, the sensor produces a light and sound signal “ALARM”. When the battery is discharged to a critical voltage, the device gives a corresponding signal. The signal is turned off by pressing the button located on the device body.

Advantages of the IP 212 fire detector

Despite its small size and limited capabilities, the smoke detector has many positive features.

So, the advantages of this device include the following:

  • simplicity and reliability;
  • affordability;
  • complete autonomy and independence from external sources power supply and control devices;
  • aesthetic appearance that will not spoil the interior of the premises;
  • no wiring required;
  • speed of reaction to the appearance of smoke;
  • ease of installation;
  • ease of maintenance;
  • safety for people and animals;
  • durability.

Fire detector IP 212 can be used as a temporary or mobile fire alarm when the room is used for a short time.

Specifications

The IP 212 smoke detector is characterized by the following indicators:

  • size - 75×40 mm;
  • weight - 100 g;
  • supply voltage - 7.5-9.5 V;
  • power source - battery or battery of the "Corundum" type;
  • operating temperature - from - 10°C to 50°C;
  • maximum air humidity - up to 95%;
  • operating hours - 24 hours a day;
  • sound signal volume - 85 dB;
  • average service life - 10 years (70,000 hours);
  • price - at various retail outlets ranges from 400-600 rubles.

If the installation, operation and maintenance rules are followed, the service life of the device can be significantly longer.

Installation and Maintenance

In order to correctly install the device, you must follow the instructions that come with all products and follow certain rules.

These rules are as follows:

  1. Compliance with safety measures when working at height. It is advisable to have safety glasses to protect your eyes when drilling into brick or concrete. In addition, a stepladder will not hurt, since working on a stool is inconvenient and dangerous.
  2. It is advisable to install the detector on the ceiling, since smoke always rushes upward. If installation on the ceiling is not possible, then it is carried out on the wall, as close as possible to its middle and to the ceiling.
  3. It is necessary to ensure reliable fastening device on the surface. To securely fix it, screws or acrylic glue are used. It should be noted that gluing can only be done on main surfaces. The plaster or wallpaper may come off the surface and the detector will fall to the floor.

As a rule, for small room In an apartment, one device in the center of the ceiling is enough. If the room is large, you can install from two to four sensors along the edges of the ceiling. Installing sensors in the corners of a room is not recommended. Smoke reaches these places last.

Despite the fact that the smoke sensor is a simple device, it requires periodic maintenance.

It is as follows:

  1. As necessary, you need to wipe the device body from dust, dirt and grease deposits. Wet wipes work well for this.
  2. Every 2-3 months it is necessary to remove dust from inside the device using a vacuum cleaner. For convenience, the detector can be removed from its mounting location.
  3. Always have 1-2 batteries in stock. Replace them in a timely manner. When leaving the apartment for a long time, remove the batteries from the device. Acid leaking from a discharged battery can irreparably damage the detector.

The IP 212 fire detector is a reliable ally of apartment owners, keeping watch while people are busy with their business or relaxing.

Video about fire smoke detector IP 212

The optical-electronic smoke detector IP 212-45 is designed for early detection of fires accompanied by the appearance of low concentration smoke in indoors various buildings and structures. The detector's scope of application extends mainly to commercial objects, such as industrial premises, hotel complexes, restaurants, cafes, shops, office buildings, shopping centers, office premises, cottages and many others.

DESIGN AND OPERATING PRINCIPLE

The fire detector IP 212-45 is an optical-electronic device that provides an alarm about the appearance of smoke at the installation site. At the same time, the internal resistance of the detector decreases and the glow of the optical indicator becomes constant. The detector is powered and the “Fire” signal is transmitted via a two-wire alarm loop (AL) and is accompanied by the activation of an optical indicator when the detector is triggered.

Indicator status

  • Standby mode - Flashing of the optical indicator with a period of (5 ± 1) s
  • "Fire" mode - Constant lighting of the optical indicator

The fire detector IP 212-45 consists of a socket and a sensor, which is a plastic case, inside of which there is an optical-electronic system and a board with radio elements. The detachable connection of the sensor to the socket ensures ease of installation and ease of maintenance of the detector. The removable smoke chamber saves time and makes the detector easy to service.

The contact base of the detector is designed on the basis of screwless contacts, which saves installation time and ensures reliable electrical contact.

Short-circuited contacts 3 and 4 of the detector provide the ability to form a “Fault” mode in the alarm loop of the receiving and control device when the sensor is removed from the socket.

The IP 212-45 detector is designed for round-the-clock and continuous operation with the following devices:

  • PPK-2;
  • “Nota”, “Signal-VK”, “Rainbow”, “Beam”;
  • Control Panel 0104065-20-1 "Signal-20";
  • Grand Master devices;
  • Granite appliances;
  • VERS devices;
  • any other receiving and control devices that provide a supply voltage in the alarm loop in the range from 9 to 30 V and perceive the “Fire” signal in the form of an abrupt decrease in the internal resistance of the detector in straight polarity to a value of no more than 1 kOhm.

SPECIFICATIONS

  • Detector sensitivity 0.05-0.2 dB/m
  • Supply voltage 9-30 V
  • Current consumption in standby mode no more than 0.045 mA
  • Response inertia no more than 9 seconds
  • Acceptable level exposure to background illumination 12000 lux
  • Allowable air flow speed up to 10 m/s
  • Noise immunity (according to GOST R 53325):
    • to nanosecond voltage pulses degree 3
    • to electrostatic discharge stage 3
    • to the electromagnetic field 3rd degree
  • Method of protection against defeat electric shock 3rd grade
  • Detector enclosure protection degree IP 30
  • dimensions∅93x46 mm
  • Detector weight 210 g.
  • Maximum relative humidity 93 ± 1%
  • Operating temperature range -45-+55 °C
  • Average service life of at least 10 years

Product code: 701148

The IP 212-45 connection diagram will help you independently install an instant fire response device. Owners of private properties and commercial properties are confident that the fire alarm will detect even the slightest amount of smoke.

Functional characteristics

The device reacts to the proportion of smoke in the air. The effect of scattering radiation from a fire by gray smoke is used here.

When measuring the smoke level, the indicator is configured to switch to the “Fire” state. At the same time, the internal resistance decreases to 1 kOhm. The indicator glows bright red, continuous in fire mode and intermittent in normal conditions.

The functionality of the alarm is checked by a special device in testing mode.

Design and operating procedure

Smoke IP 212-45 is an optical electronic device. In standby mode, the indicator indicator blinks at a frequency of 12 times per minute. When there is smoke, the internal resistance of the device decreases, the signal is transmitted through a two-wire loop, the indicator lights up brightly and constantly.

The IP 212-45 fire detector kit contains two detachable elements: a signaling device and a socket.

Structurally, the device consists of a board with radio components mounted in a plastic case and a removable smoke chamber.

The removable and detachable design is effective and time-saving during installation and technical maintenance of the device.

The product passport must contain the connection diagram for IP 212-45. A device that consumes electricity requires reliable electrical contacts. The detector has contacts without the use of screws, which adds safety in operation and reduces assembly time.

Removing the device from the socket is accompanied by the formation of a “Fault” signal in the loop connection. Technically, the signal supply is achieved by designed short-circuited contacts No. 3 and No. 4.

The alarm operates 24 hours a day without interruption.

The fire smoke detector IP 212-45 is configured to work with control and receiving devices that respond to a decrease in the internal resistance of IP 212-45 and provide voltage in the alarm zone in the range of nine to thirty volts.

Installation of the device

One fire detector serves 80 square meters premises with a ceiling height of 3.5 meters. But according to the rules fire safety Even in a ten-meter room, sensors are installed in duplicate.

The IP 212-45 sensor is connected on the ceiling, on the wall and in the space between the suspended and base ceilings. On suspended ceiling The signaling device is secured with a mounting ring. The standards for the location of devices are as follows:

  • the distance between adjacent ceiling sensors is nine meters;
  • the distance between the walls is no further than 4.5 meters;
  • the geometry of the room is required to be rectangular, without differences in ceiling heights exceeding 0.4 m and without appendixes in the contour; If the conditions are not met, the number of sensors is increased.

Installation of the device is simplified due to the versatility of the IP 212-45 connection diagram.

The detector block contains four contacts:

No. 1 - For a remote indicator.

No. 2 - Positive voltage output.

No. 3 - Negative voltage terminal.

No. 4 - To generate the “Fault” signal.

The cable for connecting one or a group of sensors is chosen to be non-flammable, for example, a low-toxic copper cable with a non-flammable mica barrier KPVSVng(A)-FRLSLTx 1 x 2 x 0.5.

The connection diagram for IP 212-45 is designed for single and group cases. When connecting the group, a resistor is soldered into the far sensor block.

The mounting fasteners tend to slip out of your hands and roll into inaccessible places. The developers of IP 212-45 provided a connection without screws. The device block is equipped with 4 holes. The cable core is stripped to the length of the upper phalanx index finger. If the installer has a ruler in his pocket, then the wire is stripped to one and a half centimeters. The prepared core is inserted into the hole, and the flag is moved to the terminal with a screwdriver. If the installation operations are carried out correctly, the technician will hear a click - this means that the core is fixed in the terminal.

Upon completion of installation of four terminals according to the connection diagram IP 212-45, they are tested for functionality.

Technical specifications

The device is small in volume - diameter 9.3 centimeters and height 4.6 cm. The assembled weight is 210 grams. When a structure falls from the ceiling, physical injury is excluded.

Manufacturers guarantee a ten-year service life of the alarm.

The interval between the moment of smoke and the operation of the device does not exceed nine seconds. This time is 4-6 times less than the linear horizontal speed of fire spread both in a residential building and in an industrial building.

The disadvantage of IP 212-45 is that the device reacts to both smoke and dust. To avoid false triggering of the device, the chamber is cleaned with a vacuum cleaner. Electronic equipment is vacuumed in the “blow” mode. Periodicity preventive measures- once every six months.





Description Rubezh IP 212-45 with US-02

The optical-electronic waterproof smoke detector IP 212-45 is designed for early detection of fires accompanied by the appearance of low concentration smoke in enclosed spaces of various buildings and structures. The detector is powered and the “Fire” signal is transmitted via a two-wire alarm loop and is accompanied by the inclusion of an optical indicator when the detector is triggered. The detector does not respond to changes in temperature, humidity, the presence of flame, natural or artificial light. Modern optical-electronic smoke detector of the “Marco” series with visual indication of the detector status, European housing design and screwless contacts.

Improved consumer properties:

  • The detector uses a unique microcircuit of its own design that digitally processes optocoupler signals;
  • a new improved dust compensation algorithm that increases noise immunity and eliminates false alarms;
  • horizontal and vertical smoke exhaust ensures rapid response of the detector when the first signs of smoke appear;
  • blinking LED in standby mode;
  • small overall dimensions;
  • wide range of supply voltages from 9 to 30 V;
  • low current consumption – no more than 0.045 mA;
  • convenient testing using a button makes the task of technicians as easy as possible;
  • The detector body is made of shock-resistant and wear-resistant ABS material.

    The detector is designed for round-the-clock and continuous operation with control and control devices that provide a supply voltage in the alarm loop in the range from 9 to 30 V and perceive the “Fire” signal in the form of an abrupt decrease in the internal resistance of the detector in straight polarity to a value of no more than 1000 Ohms, such such as Granit, Grand Master, VERS PK, Signal-20, Signal-20P, etc.

    The detector performs the following functions:

  • smoke concentration measurement;
  • digital processing using special algorithms of measurement results and making a decision to switch to the “Fire” mode;
  • reducing internal resistance in the “Fire” mode to 1 kOhm;
  • performance testing using a special device;
  • LED indication of operating modes.

    The “Fire” signal remains after the end of exposure to the smoke detector. Reset is performed from the control panel by turning off the power supply to the detector for a period of at least 2 seconds.

    The connection between the sensor and the socket is detachable. Circular contacts allow you to install the detector without orienting it relative to the socket. The socket is unified and allows you to install any Rubezh TM detector without rewiring the system. Connecting the negative wire of the AL to contacts 3 and 4, short-circuited through the detector, allows you to receive a “malfunction of AL” signal on the control panel when removing the detector from the socket.

    The detector can be installed on a suspended ceiling using a special socket combined with a mounting ring.

    The screwless method of fastening wires using a button clamp ensures reliable contact and ease of installation.

    When connecting a detector to the alarm loop of a control panel that has the function of determining the number of triggered detectors (double trigger function), it is necessary to use an additional resistor Rd. The value of the additional resistor depends on which control panel the detector is connected to and is calculated based on the resistance of the device loop in the “Fire” and “Attention” modes. Instead of an additional resistor, it is possible to use a matching device US-01, installed in the detector socket and containing a resistor (the value is determined when ordering) and a contact block.

    The detector can work with devices that have a four-wire switching circuit. For this purpose, the US-02 matching device is used. It is installed in the housing of the standard detector socket.

    The detector provides the ability to connect a remote optical signaling device (VUOS).

    CONNECTION DIAGRAM OF IP 212-45 DETECTORS TO THE CONTROL PKOP ALARM LINE

    If the double triggering function is not required, then the additional resistor Rd is not installed. Wherein control panel must have a current limiting function in the “Fire” mode to 20 mA to avoid failure of the detector.

    Technical characteristics Rubezh IP 212-45 with US-02

    • Unit: 1 piece
    • Dimensions (mm): 94x94x46
    • Weight (kg): 0.21

    • Detector sensitivity: 0.05-0.2 dB/m
    • Supply voltage: 9-30 V
    • Current consumption in standby mode: no more than 0.045 mA
    • Response delay: no more than 9 seconds
    • Permissible level of exposure to background illumination: 12000 lux
    • Allowable air flow speed: up to 10 m/s
    • Noise immunity (according to GOST R 53325): 4 degree
    • Detector enclosure protection degree: IP 30
    • Overall dimensions: Ø94x46 mm
    • Detector weight: 210 g.
    • Maximum relative humidity: 93 ± 1%
    • Operating temperature range: -45 - +55 °C
    • Average service life: at least 10 years